copy of EM 3 (12-38 kW) palnik gazowy Lamborghini Lamborghini
  • copy of EM 3 (12-38 kW) palnik gazowy Lamborghini Lamborghini

EM 16 (80-160 kW) Lamborghini gas burner

Gas burner EM 16-E.D4 ¾ ", power from 80 to 160 kW, powered by natural gas or LPG. A product of the Italian brand LAMBORGHINI

Wybierz rampę gazową
help_outlineAsk about product
EM 16 (80-160 kW) Lamborghini gas burner

EM 16 (80-160 kW) Lamborghini gas burner

Gas burner EM 16-E.D4 ¾ ", power from 80 to 160 kW, powered by natural gas or LPG. A product of the Italian brand LAMBORGHINI

I accept privacy policy rules  

 

Safe and secure shopping

 

Fast shipping

 

Satisfaction guaranteed

Lamborghini EM gas burners, thanks to their small size and large working area, are ideal for small boiler rooms with low and medium pressure boilers.

Construction:

Lamborghini EM series burners are characterized by reliability, durability and low gas consumption with high efficiency. They are available in the power range from 12 kW to 320 kW. Energy consumption and emissions can be reduced to a minimum by installing burners with modern electronic control and regulation.

Characteristics of the EM 16 gas burner:

  • single-stage (EM) burners,
  • for pressure boilers,
  • can be used in new installations, as well as for reconstruction and modernization of old boilers,
  • gas path with a stabilizer, double valve and filter,
  • low CO emissions 2
  • adjustment of the combustion head (except for the EM 26-E - EM 35-E model),
  • soundproofed casing,
  • compact size,
  • versatility thanks to the possibility of connecting various type of gas,
  • supplied in 2 packages (burner + gas ramp),
  • easy installation thanks to a movable flange,
  • power supply: natural gas or LPG (for model EM 16-E - 26-E conversion kit is needed.

Description of the burner structure

Gas pressure switch

Air pressure switch

Ignition transformer

Operating valve

Security box

Air valve

Servo control

Controller

Combustion head

Plate with components

Flange for attaching to the boiler

Safety valve

Fan

Engine

Cover

Burner body

Burner working area

In order to be sure that the burner will fit your boiler or heater, check on the basis of the work area diagram whether the pressure of the burner fan will be able to overcome the resistance of the boiler combustion chamber. If you have any questions or doubts as to whether this burner will be suitable for your device, please contact our company. We will help you find the most optimal solution. P & gt;

Dimensions:

A

310

B

282

C

480

D (MIN)

60

D (MAX)

150

E

215

Ø F

108

Ø G

115

Ø H (MIN)

150

Ø H (MAX)

200

I

M8

L*

535

M*

210

Ø

3/4"

* Dimensions refer to the burner with a gas draft of 20 mbar.

TECHNICAL DATA:

Heating power

80-160 kW

Air flow

8 - 16,1 m³/h

Connection diameter

⌀ ¾"

Pressure on the Web

18 mbar

Max. Pressure in the network

360 mbar

Power

230 V / 50 Hz

Fan energy consumption

110 W